Stadtsparkasse, Munich

Chilled beam ACBLA

→Active chilled beam for cooling with high thermal room loads, via convection and primary air
→ Suitable for visible installation below the ceiling
→ Power customisation possible by selecting different power categories
→ For cooling medium in water quality according to VDI 2035
→ Air intake from the room is from below through the perforated room screen; air connection on the front side

Chilled beam ACBLA

→ 21 units in two lengths: 4 pcs. 3000 x 574 x 120 mm [L x W x H], 17 pcs. 1800 x 574 x 120 mm [L x W x H]
→ Housing made of sheet steel, coated white acc. to RAL 9003, designed as a closed system towards the ceiling with perforated room screen panel
→ Integrated mounting rail incl. retaining clamps, room screen panel retractable for maintenance purposes
→ Air connection with diameter DN 100
→ Cooling coll: tubes made of copper with aluminium fins, mechanically expanded, operating pressure max. 10 bar
→ Medium connections (ø 15 mm) made of copper pipe, suitable for solder, clamp or crimp connections, medium connections at the front, max. operating temperature 70 °C
→ Water supply/return 17 °C/19 °C
Room temperature 26 °C
Supply air temperatur 18 °C
Suppl air volume 135 m²/K
Capacity ACBLA 1800 mm 1.2 W
Capacity ACBLA 3000 mm 1.8 W

Location

München

Finished

2025

Building owner

Stadtsparkasse, Munich

Planner

IBH Ingenieurgesellschaft, Maisach

Built-in products

Cooling beam ACBLA